What is a Reactive Load Bank and When Should You Specify One?

titan-1766kva

A “reactive” load bank includes inductive (lagging power factor) loads consisting of iron-core reactive elements which, when used in conjunction with a resistive load bank, create a lagging power factor load. Typically, the inductive load will be rated at a numeric value 75% that of the corresponding resistive load. When applied together, a resultant 0.8 power factor load is provided. That is to say, for each 100KW of resistive load, 75KVAR of inductive load is provided (other ratios are possible to obtain other power factor ratings).

While resistive-only loads simulate lighting and heating loads, inductive loads are used to simulate real-life mixed commercial loads consisting of lighting, heating, motors, transformers, etc.

So, for a facility that has large electric motors and/or a substantial number of transformers, specifying a resistive/inductive load bank will allow for the emergency power source to be tested in a manner that more-closely resembles “real-world” conditions. This testing may be performed with a portable load bank, on a periodic maintenance schedule, or via a load bank integrated into the facility’s electrical system. Why does it matter? A “real-world” test can identify problems with the EPSS, such as issues resulting from the impact of reactive currents on generator/voltage regulator performance, as well as effects on conductors and switchgear.

Using the facility’s loads for periodic EPSS tests is a good idea and highly-recommended. Building loads offer the most realistic test by exercising the entire power system with actual loads. However, it is often the case that existing building loads may not be sufficient, ie.: the facility is not fully built out, or is not operating with high-enough loads when the tests need to be performed. Facility loads are also continuously changing, which may not allow for controlled load application to properly test the EPSS. The facility owner may also prefer to perform these tests offline, to avoid any potential power disruptions to the facility.

Where there is a requirement to test an emergency power source with realistic loads, including not only resistive loads but also reactive loads, and where the facility owner prefers to perform the tests in an offline, controlled manner, a resistive/reactive test load bank provides a great solution.


Simplex manufacturers stationary and portable load banks of any load rating, resistive and/or inductive, for voltage applications up to 15kV.

Learn more about load banks and how they are applied to emergency generator installations:

For additional support with a custom requirement, give us a call – we’re ready to help!